Wiring Connections
3-2 Guard-It
TM
Owner's Manual
3.3 Phone Line Connection
Plug one end of the supplied telephone extension cord into the telephone line
jack located to the left of the connector block (
not the programming jack located
on the front panel). Plug the other end of this same cable into a telephone line
(RJ11) jack.
I Caution:
The phone line must be such that a standard telephone set can work on it.
Certain in-house PABX phone systems have “digital” line connections which
can damage the product!
Ideally this phone line should be for the exclusive use of the Guard-It
TM
autodialer. However, the product will generally function if there is an extension
phone on the same line, as long as that extension phone is not in use when it is
time for the Guard-It
TM
to place or receive a phone call.
3.4 Input Signal Connections
The four signal inputs on the Product can be used with several different types of
input signals, in any combination.
3.5 Connecting Unpowered ("DRY")
Contact Inputs
Connect unpowered contact inputs as shown in the diagram. Each input has
two input connection points. The points marked “C” are internally connected
together and to common ground.
M Warning:
Before making any such connections, verify that there is no electrical power
present on the signal wires, otherwise serious damage to the product could
result.
3.6 Connecting Analog or Digital Logic
Signal Inputs
Refer to Appendix A regarding analog signal inputs and Appendix B regarding
digital logic signal inputs.